Page 1 09/14/2007
The Hydroguard
®
XP LFMM430 series is a temperature actuated
mixing valve designed for use in hot water distribution systems, in
compliance with ASSE 1017.
Maximum Operating Pressure ............. 125 psi (861 kPa)
Maximum Hot Water Temperature .......200°F (93°C)
Minimum Hot Water Supply Temp ....... 5°F (3°C) Above Set-Point*
Temp. Adjustment Ranges
** Standard:........................................ 90 - 160°F (32 - 71°C)
Low: ..................................................... 60 - 90°F (16 - 32 C)
Hot Water Inlet Temperature Range .....120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ... 40 - 80°F (4 - 27°C)
Listing......................................................... ASSE 1017
Certified .................................................... CSA B125
* With Equal Pressure
**
Low limit cannot be less than the cold water temperature.
For best operation, hot water should be at least 5°F (3°C)
above desired set point.
Specifications n
HYDROGUARD
®
XP
Master Tempering Valves
Series LFMM430
Technical Instructions
IS-P-MM430
Advanced Thermal Activation
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-
mation can result in death, serious personal injury,
property damage, or damage to the equipment.
Keep this Manual for future reference.
You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual is
not consistent with local building or plumbing codes, the local
codes should be followed. Inquire with governing authorities for
additional local requirements.
WARNING
!
WARNING
!
Flush all pipes thoroughly before installation. Installation and
field adjustment are the responsibility of the installer.
NOTICE
Description n
WARNING
!
Need for Periodic Inspection and Yearly Maintenance:
Periodic inspection and yearly maintenance by a licensed con-
tractor is required. Corrosive water conditions and/or unauthor-
ized adjustments or repair could render the valve ineffective for
service intended. Regular checking and cleaning of the valve’s
internal components and check stops helps assure maximum
life and proper product function. Frequency of cleaning and
inspection depends upon local water conditions.
FAILURE TO COMPLY WITH PROPER INSTALLATION AND
MAINTENANCE INSTRUCTIONS COULD CONTRIBUTE TO THE
VALVE FAILURE.
This Hot Water Master Tempering Valves cannot be used for
tempering water temperature at fixtures. Severe bodily injury
(i.e., scalding or chilling) and/or death may result depending
upon system water pressure changes and/or supply water
temperature changes. ASSE standard 1016, 1069 or 1070 listed
devices should be used at fixtures to prevent possible injury.
These Hot Water Tempering Valves are designed to be
installed at or near the boiler or water heater. They are not
designed to compensate for system pressure fluctuations and
should not be used where ASSE standard 1016, 1069 or 1070
devices are required. These valves should never be used to
provide “anti-scald” or “anti-chill” service.
The components of the system must be of materials with a
construction capable of withstanding the high limit output tem-
peratures of the water heating source.
WARNING
!
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - Technical Instructions

MM430_For_PS-Sheet_Test_1.pdfPage 1 09/14/2007The Hydroguard® XP LFMM430 series is a temperature actuated mixing valve designed for use in hot water d

Seite 2 - Capacity n

1. Installation should be in accordance with acceptable plumb-ing practices. Flush all piping thoroughly before installation. Installation and field

Seite 3 - Parts List - LFMM435 n

1245 & 63871234 & 5678Parts List - LFMM431, LFMM432, LFMM433, LFMM434 nParts List - LFMM435 nIndex DescriptionLFMM431 LFMM432 LFMM433 LFMM4341

Seite 4 - Warranty n

3. Pull out plunger using a pair of pliers.4. To remove funnel, you will need a deep socket wrench and funnel removal tool.5. Reassemble in reverse