Description n
Capacity n
Triple Valve PowerStation
™
Capacity up to 416 gpm
Technical Instructions
IS-P-SF-TVPS
Advanced Thermal Activation
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp.* ................... 5°F (3°C) above set point
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)
Temperature Adjustment Range *** ................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valves only) .......................... ASSE 1017, CSA B125
* With Equal Pressure
** Minimum flow when Hi/Lo is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.
Specifications n
Flow Capacity at 50-50 Mixed Ratio
Pressure Drop Across Valve
Model
Min. Flow
CV
5psi 10psi 20psi 30psi 45psi 60psi
to ASSE 1017
(34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
SH1434TV and
LFSH1434TV
1 gpm
62.00
139 gpm 196 gpm 277 gpm 340 gpm 416 gpm 480 gpm
4 lpm 526 lpm 742 lpm 1049 lpm 1287 lpm 1575 lpm 1817 lpm
PowerStation
™
is a complete, fully assembled water tempering system,
designed to provide safe water throughout commercial and institutional
facilities. PowerStation
™
features the HydroGuard
®
XP MM430 or LFMM430
and SH1430 or LFSH1430 master tempering series valves which utilize
paraffin-based actuation technology to sense and adjust outlet temperature.
Each PowerStation
™
is mounted on heavy-duty, welded struts and factory
tested as a complete system. Each PowerStation
™
includes an engineer
specified circulator, GFCI outlet, combination temperature/pressure gauges
and Powers' triple-duty checkstops. Optional equipment includes an
Aquastat.
WARNING: TO ENSURE THE
ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:
• Properly size each valve based on the indi-
vidual application.
• Properly design the recirculation system to
minimize pressure and temperature variations.
• Conduct an annual maintenance program to
ensure proper operation of all critical com-
ponents.
THIS VALVE MUST BE USED IN
CONJUNCTION WITH TEMPERATURE
ACTUATED POINT-OF-USE DEVICES THAT
COMPLY WITH ASSE 1016, 1069, OR 1070.
FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING
IN IN JURY OR DEATH.
!